 TEST METHOD FOR SULFITE IN INDUSTRIAL WATER  (RANGE: 0-200 & above mg/L SO3)

BACKGROUND OF THE TEST:

In boiler water treatment, numerous oxygen scavengers 

are used. Sodium Sulfite is considered as one of the 

most effective scavenger among all. Accordingly, certain 

residuals of sulfite are maintained and measured in 

boiler feed water before economizer and/or in the 

boiler drum to ensure that dissolved oxygen levels are 

NIL.

Nuclotrasis offers user friendly test method with ease of 

handling the relevant reagents and other equipment in 

which Iodine is liberated in an acidic medium of the 

sample upon addition of Iodide ion with Titrant. The 

produced iodine reacts with sulfite residuals present in 

the sample. Upon end point that is when all sulfite 

residuals are completely oxidized by iodine produced 

earlier, the liberated excess iodine eventually develops 

blue color upon reaction with starch indicator and the 

volume of Titrant used is noted. 

REAGENTS/EQUIPMENTS/APPARATUS:

 Provided 5 mL & 10 mL marked glass vial (Item 

Code: 02-01)

 NUCLOTRASIS SULFITE-I Reagent

(Item code: 01-05-01)

 NUCLOTRASIS SULFITE-II Test Indicator Reagent 

(Item code: 01-05-02)

 NUCLOTRASIS SULFITE-III Test Titrant Solution 

(Item code: 01-05-03)

SAMPLE COLLECTION & PREPARATION

 Make sure to immediately analyze the sample after 

collection of sample.

 Ensure to collect sample in a suitable and 

designated bottle for a specific sample.

 Thoroughly rinse the sample bottle with current 

sample and fill the sample by allowing slight 

overflow and immediately tighten the cap.

 Prevent agitation of the sample and exposure to air 

as the test is sensitive to the air.

TEST PROCEDURE:

1. We recommend selecting the sample volume in 

the provided glass vial (Item Code: 02-01)

based on your expected/desired sulfite residuals 

range from the chart below.

2. Then add 10 drops of NUCLOTRASIS SULFITE-I 

Reagent (Item code: 01-05-01) and swirl to 

mix.

3. Then add 3 drops of NUCLOTRASIS SULFITE-II 

Test Indicator Reagent (Item code: 01-05-02)

and swirl to mix.

4. Now start adding NUCLOTRASIS SULFITE-III 

Test Titrant Solution (Item code: 01-05-03)

drop wise while gently swirling the flask and 

while counting number of drops added until a 

permanent faint blue color appears. 

5. Note the number of drops added and multiply 

with multiplication factor mentioned in above 

chart against selected sample volume.

6. Report the reading as ppm (mg/L) or as required 

by the system.

REFERENCES:

1. ASTM Manual of Industrial Water, D1339, 

Method C

2. Standard Methods for the examination of 

Water and Wastewater.

Range

(mg/L as Na2SO3)

Sample volume

 (mL)

Multiplication Factor

For result as Na2SO3

0-40 10 3.15

20-80 5 6.28

80-200 2 15.7

200-400 and above 1 31.4

Range

(mg/L as SO3)

Sample volume

 (mL)

Multiplication Factor

For result as SO3

0-40 10 2

20-80 5 4

80-200 2 10

200-400 and above 1 20